Single-Stack Systems
—
by
(1) Single-stack systems may be used under the following conditions- a) all soil and waste branch pipes shall be separately connected to the vertical soil stack; b) the minimum depth of water-seals shall be 75 millimetres for waste-water fittings, and 50 millimetres for soil-water fittings; c) the waste-pipe used in conjunction with a 32-millimetre-diameter trap…
-
Protection Of Waste-Water Traps
—
by
(1) In the one-pipe system, the water-seal of the trap of every waste-water fitting shall be protected by means of an anti-siphon pipe : Provided that, where horizontal waste-pipes are back-vented as described in section 46, the anti-siphon pipes may be omitted. (2) In the one-pipe system, the water-seal of the trap of every waste-water…
-
Ventilation Of Soil-Water Fittings
—
by
Where several soil-water fittings are connected to a branch soil-pipe which is provided with a vent connected to such branch soil-pipe immediately short of the farthest soil-water fitting on such branch, and such vent is connected to another vent at a point not less than 150 millimetres above the highest water-level possible in such soil-water…
-
Protection Of Soil-Water Traps
—
by
Subject to the provisions of section 46, the water-seal of the trap of a soil-water fitting shall, in the following cases, be protected by means of an anti-siphon pipe of such dimensions and location as are section 40, respectively, that is to say where such soil-water fitting- a) discharges into an unventilated sewer or soil-pipe…
-
Anti-Siphon Pipes
—
by
(1) Every individual anti-siphon pipe shall be connected to the soil-pipe or waste-pipe which it serves on the outlet side of the trap obliquely in the direction of flow of the last-mentioned pipe at a point not less than 75 millimetres or more than 750 millimetres from the crown of the trap. (2) Such anti-siphon…
-
Inter Connexion Of Vents From Soil And Waste-Fittings
—
by
Where two pipe system is used, a pipe which ventilates a soil-pipe or fitting and a pipe which ventilates a waste-pipe or fitting shall not be connected to each other.
-
Branch Vents And Anti-Siphon Pipes
—
by
Every vent and every anti-siphon pipe shall, unless carried up independently, be connected to a main vent at a point at least 150 millimetres above the top of the highest fitting which the main vent serves.
-
Gradient Of Vents And Anti-Siphon
—
by
Every vent and every anti-siphon pipe shall be so graded as to provided a continuous fall without the interposition of a trap from its open end to the point of connexion to the waste-pipe, soil-pipe, private sewer or combined private sewer which it serves.
-
Ventilation Outlets
—
by
(1) Every vent-pipe or anti-siphon pipe shall be carried upwards without diminution of diameter to a height of at least 4,5 metres above finished ground-level, 300 millimetres above place of emergence through the roof, or 1 metre above eaves-level, whichever is the greatest height, or to such greater height or to such position as the…